#Configurable switching point: 1. Open on rise or fall in pressure
2. Hysteresis of set-point
Measurement units (Pa, kPa, mmWC, inWC, mbar).
Measurement ranges (4 ranges per model).
Output signal (0 to 10 V, NO/NC).
Span and zero point calibration.
DPI options include:
Up to 2 relays, which can be configured separately.
Autozero calibration.
Specification
| Accuracy (from FS): | 1.5 % (0.7 % with span point calibration) (including: general accuracy, temperature drift, linearity, hysteresis, and repetition error) |
| Long term stability, typical 1 year: | 1 Pa (8 Pa without autozero element -AZ) |
| Zero point calibration: | automatic with autozero element (-AZ) or by pushbutton |
| Supply voltage: | 2135 VDC / 24 VAC 10 % (without -AZ option) |
| Current consumption: | 35 mA + relays (7 mA each) + AZ (20 mA) + 010 V output (10 mA) |
| Output signals: | 010 V, L min 1 k |
| Operating temperature: | -10+50 C |
| Response time: | 0,510 s |
| Protection standard: | IP54 |
Specification
| Accuracy (From FS) | +-1.5% |
| Zero point Calibration | Automatic with autozero element (-AZ) or by push button |
| Supply Voltage | 21-35 VDC/ 24VAC+-10 % |
| Current Consumption | 35 mA + relays (7mA each) + AZ (20 mA) + 0 to 10V o/p (10 mA) |
| Output Signal | 0 to 10V |
| Relay output | 250 VAC / 30VDC/6 A |
| Operating Temperature | -10 to +50 DegC |
| Response Time | 0.5 to 10s |
| Protection Class | IP54 |
| Display | 3 1/2 digit LCD backlit display Size: 46.0 W x 14.5 H mm |
| Measuring Ranges: | |
| +-500 | -100 to 100 / -250 to 250 / -300 to 300 / -500 to 500 |
| 2500 | 0 to 100 / 0 to 250 / 0 to 1000 / 0 to 2500 |