The CDT 2000 Carbon Dioxide Transmitter is designed for HVAC building services. The CDTMOD-2000 series detects carbon dioxide and temperature using the industry-standard NDIR measuring technology. In addition, absolute humidity measurement is provided as an option in the same instrument. Modbus network configuration is also feasible. According to the ABCTM logic, the room in which the transmitter is utilised must be empty for four hours a day in order for the indoor CO2 concentration to decrease to the outside level.
Specification
Calibration | Automatic self-calibration,ABC LogicTM or continuous comparison (DC) |
Brand | HK Instruments Oy |
Model Name/Number | CDT2000 |
Supply Voltage | 24 VDC/VAC +-10 % |
Protection Standard | IP54 |
Output Signal 2 | 0/2-5/10 V (linear to Temp) |
Output Signal 1 | 0/2-5/10 V (linear to CO2) |
Optional Output Signal 4 | 4-20 mA (linear to Temp) (A model) |
Optional Output Signal 3 | 4-20 mA (linear to CO2) (A model) |
Operating Temperature | 0 To +50 Degree C |
Measuring Units | ppm,Degree C |
![]() |
PARSHVI TECHNOLOGY (INDIA) PRIVATE LIMITED
All Rights Reserved.(Terms of Use) Developed and Managed by Infocom Network Private Limited. |