Product Description
Accuracy (from applied pressure): (model 2500) | Pressure < 125 Pa = 1 % + 2 Pa Pressure > 125 Pa = 1 % + 1 Pa |
Accuracy (from applied pressure): (model 7000) | Pressure < 125 Pa = 1.5 % + 2 Pa Pressure > 125 Pa = 1.5 % + 1 Pa |
| Measuring units: | Pressure: Pa, kPa, mbar, inchWC, mmWC, psi Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min |
| Control signal: | 010 VDC |
| Output signal for pressure or air flow (selectable via menu): | 010 VDC 420 mA |
| PID-parameters: | Adjustable via menu |
| Zero point calibration: | Automatic with autozero element (-AZ) or by pushbutton |
| Supply voltage: | 24 VDC 10 % / 24 VAC 10 % |
| Power consumption: | < 1.0 W |
| Operating temperature: | -20+50 C (with autozero calibration -5+50 C) -40+50 C (-40C model) |
| Protection standard: | IP54 |
Wide Measuring Range and VersatilityWith a scale range from -500 Pa to +5000 Pa, the DPT-Dual-MOD Two Pressure Sensor accurately measures both low and high-pressure differentials. Suitable for monitoring air and non-corrosive gases, it is ideal for HVAC systems, clean rooms, and ventilation controls, providing versatility for multiple industrial or laboratory applications.
Reliable Performance and Rapid ResponseEngineered for reliability, this sensor delivers results in under 100 milliseconds and maintains high accuracy at 1.5% of full scale. Its digital display ensures easy readings, making it suitable for dynamic environments requiring quick and accurate pressure monitoring.
Easy Integration and InstallationEquipped with selectable output signals (4-20mA, 0-10V), M12 4-pin electrical connection, and supplied mounting hardware, integration into existing control systems is straightforward. The panel mount format, 1/8 NPT thread, and lightweight, compact build further simplify installation, supporting industrial automation needs.
FAQs of DPT-Dual-MOD Two Pressure Sensor:
Q: How do I connect the DPT-Dual-MOD Two Pressure Sensor to my control system?
A: The sensor features a standard M12, 4-pin electrical connector for rapid hookup. You can select either the 4-20mA or 0-10V output signal for compatibility with most industrial controllers. The included mounting bracket and screws streamline panel installation.
Q: What types of media can the sensor accurately measure?
A: This pressure sensor is designed specifically for measuring the pressure of air and non-corrosive gases, making it unsuitable for liquids or corrosive gas applications.
Q: When should the sensor be used in an application?
A: Deploy this sensor whenever precise monitoring of differential pressure is needed, especially in HVAC, clean room, or process control environments where rapid response and digital readout are beneficial.
Q: Where can the sensor be installed within a facility?
A: With its IP65 protection and compact size, the sensor can be panel-mounted in industrial, laboratory, or commercial setups exposed to dust or splashes, within the rated temperature range.
Q: What is the process for calibrating or adjusting the sensor?
A: The digital interface allows for straightforward adjustment. For calibration, follow the instructions in the user manual provided by your distributor or supplier to ensure continued measurement accuracy.
Q: What are the benefits of choosing this model over standard pressure sensors?
A: Key advantages include selectable analog output, rapid response time, excellent accuracy (1.5% FS), digital display, robust IP65 protection, and ease of installationall enhancing system reliability and user convenience.