Differential Pressure Transmitter, DPT-CTRL

Differential Pressure Transmitter, DPT-CTRL

Product Details:

  • Product Type Digital
  • Weight 150 g Grams (g)
  • Connection 3-wire (V Out, 24 V, GND)
  • Pressure 2500 & 7000 Pa
  • Application commonly used in HVAC/R systems
  • Accuracy 1 % + ±2 Pa %
  • Color white
8500.00 INR/Piece
X

Price And Quantity

  • 1 Piece
  • 8500.00 INR/Piece

Product Specifications

  • commonly used in HVAC/R systems
  • Controlling differential pressure or air flow in air handling systems
  • ABS
  • less than 1.0 W Watt (w)
  • 1 % + ±2 Pa %
  • Digital
  • 150 g Grams (g)
  • white
  • 24 VAC or VDC, ±10 % Volt (v)
  • 3-wire (V Out, 24 V, GND)
  • 90.0 x 95.0 x 36.0 mm Millimeter (mm)
  • To control the constant pressure or flow of fans, VAV systems or dampers
  • 90.0 x 95.0 x 36.0 mm
  • Electrical
  • 2500 & 7000 Pa

Trade Information

  • All India
  • Meets requirements for CE marking: EMC Directive 2014/30/EU RoHS Directive 2011/65/EU WEEE Directive 2012/19/EU

Product Description

DPT-Ctrl is a multifunctional PID controller with differential pressure or air flow transmitter.
DPT-Ctrl enables to control constant pressure or flow of fans, VAV systems or dampers. Its two lined display shows the direction of the control output and the measurement value at the same time. It is possible to select either current or voltage for both the control output and the differential pressure or flow output. The optional autozero function eliminates the need for periodic manual zero point calibration.

 

DPT-Ctrl series devices include:

  • Control differential pressure or air flow in duct or across centrifugal fans
  • All parameters (PID) are adjustable via menu
  • Differential pressure or air flow transmitter (selectable via menu)
  • Measure and monitor differential pressure or air flow in duct or across centrifugal fans


Specification

Accuracy

(Model 2500) For Pressure less than 125 Pa= 1% +  +- 2PA

(Model 2500) For Pressure greater than 125 Pa= 1% +  +- 1PA

(Model 7000) For Pressure less than 125 Pa= 1.5% +  +- 2PA

(Model 7000) For Pressure greater than 125 Pa= 1.5% +  +- 1PA

Measuring Range

Pressure: Pa, kPa, mbar, inchWC, mmWC, psi

Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min

Supply Voltage

24 VDC/ 24VAC+-10 %

Current Consumption

Less than 1 W

Output Signal

0 to 10VDC or 4 to 20mA

Control Signal

0-10 VDC

Operating Temperature

-20 to +50 DegC

Response Time

1.0 to 20s

Protection Class

IP54

Display

2 Line Display (Direction of control output & Pressure or air flow)

Size: 46.0 W x 14.5 H mm

Measuring Ranges:

 

2500

0 to 2500 Pa

7000

0 to 7000 Pa


PARSHVI TECHNOLOGY (INDIA) PRIVATE LIMITED

* Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.



Back to top
PARSHVI TECHNOLOGY (INDIA) PRIVATE LIMITED All Rights Reserved.(Terms of Use)
Developed and Managed by Infocom Network Ltd.(Terms of Use)
Developed and Managed by Infocom Network Ltd.